MS6 REDUCED VOLTAGE STARTER

Page 14

DRY CONTACT RELAY OUTPUTS
10

Fault Relay Common

11

Fault Relay N.C.

12

Fault Relay N.O.

The fault relay is energized in a NO
Fault
condition. In a fault condition or
a case of power loss the relay will de-
energize and the contacts will go to
there normal condition indicating a
fault.

13

Bypass Relay Common

14

Bypass Relay N.O.

This relay is used to control a by-pass
contactor either directly or indirectly if
the coil current of the by-pass contactor
is to large (>5amps). This relay will
energize once the Opal Pro has phased
full on and the motor current has
dropped below 110% of the nameplate
current.

15

Shorted SCR Relay Common

16

Shorted SCR Relay N.C.

17

Shorted SCR Relay N.O.

This relay is energized when a shorted
SCR is detected and should be used to
trip a shunt trip breaker.

18

Run Relay Common

19

Run Relay N.O.

This relay is energized when the unit is
running

20

Reverse Relay Common

21

Reverse Relay N.O.

This relay is energized when the unit is
running is the reverse mode

ANALOG I/O (not isolated)
22

Analog Input ( 0 to 10VDC)

23 Analog

Common

24

Analog Output (0 to 5VDC, max 5mA)

25 Analog

Common