MS6 REDUCED VOLTAGE STARTER

Page 26

12

Analog

I/O

1201 Analog

Output

-

This parameter designates what signal will be sent out the analog
output

-

Current reference means the current reference that the Opal is
currently using (0-5volts = 0 – 615% motor nameplate current)

-

Current feedback means that the actual motor current will be sent
(0-5volts = 0-615% motor nameplate current)

-

Overload level means that the present calculated thermal capacity
will be sent (0-5volts = 0-100% of capacity)

-

Phase Angle means that the current phase angle will be sent (0-
5volts = 0-180 degrees)

Current Reference
Current Feedback
Overload Level
Phase Angle

13

Motor

Data

1301

Motor

Amps

- this should be the name plate full load amps of the motor

5 – 1100 Amps

Read\Write

1302

Motor

Volts

- this should be the name plate voltage of the motor

240 – 600 Volts

Read\Write

1303

Service

Factor

- this should be the name plate service factor of the motor

1.00 – 1.30

Read\Write

14

Communications

1401

Modbus Slave Node
-

This is the slave node that the Opal will be seen as

-

This parameter is only accessible if a Modbus Slave card is
installed in the Opal

1 – 7

Read\Write

1402

MB Slv Baud Rate
-

This is the baud rate that the MB Slave card will attempt to
communicate

-

This parameter is only accessible if a Modbus Slave card is
installed in the Opal

300 Kbaud
1200 Kbaud
2400 Kbaud
4800 Kbaud
9600 Kbaud
19200 Kbaud
38400 Kbaud
57600 Kbaud

Read\Write

1403

DeviceNet

MacID

-

This is the DeviceNet MacID that the Opal will be seen as

-

This parameter is only accessible of a DeviceNet Slave card is
installed in the Opal

0 – 31

Read\Write

1404

DeviceNet Slv Baud Rate
-

This is the baud rate that the DeviceNet Slave card will attempt to
communicate

-

This parameter is only accessible of a DeviceNet Slave card is
installed in the Opal

125 Kbaud
250 Kbaud
500 Kbaud

Read\Write

1405

DH+ Station Address
-

This is the station address that the Opal will be seen as

-

This parameter is only accessible if a DH+ card is installed

1 - 32

Read\Write

1406

DH+ Baud Rate
-

This is the baud rate that the DH+ card will communicate at

-

This parameter is only accessible if a DH+ card is installed

57.6 Kbaud
115.2 Kbaud
230.4 Kbaud

Read\Write