MS6 REDUCED VOLTAGE STARTER

Page 25

1006

Jog Accelerating Current Limit
-

This is the current limit that will be used when in the jog
mode

-

When jog is initiated the current will ramp up to this
value in 1 second and remain here for the amount of time
specified in parameter 1008.

0% - 400%

Read\Write

1007

Jog Current Limit
- This is the current limit that will be used in jog mode after
the acceleration time has elapsed

0% - 400%

Read\Write

1008

Jog Ramp
-

This is the amount of time that the starter will regulate the
accelerating current set in parameter 1006 in jog mode
before dropping to the current limit set in parameter
1007

-a value of zero will cause the starter to go directly to
regulating the current set in parameter 1007

0 – 5 seconds

Read\Write

11

Stop

Control

1101

Stop

Mode

-

Coast means that the Opal will inhibit firing of the
SCR’s as soon as the stop command is received

-

Soft Stop means that the Opal will ramp down the
current in the amount of time specified in parameter
1102

Coast
Soft Stop
DC Injection

Read\Write

1102

Sft Stop Step
-

This is the amount of motor voltage that the output
will step down to when a stop is commanded. If this
value is set to high the motor will go through a state of
instability.

50% – 85%

Read\Write

1103

Sft Stop Rmp
-

This is the amount of time that it will take to ramp the
voltage down from the step voltage to 35% of the
motor voltage

2 – 60 seconds

Read\Write

1104

DCI

Current

- this is the amount of current that will be regulated during
DC Injection stopping (represented as a percentage of
nameplate current)

100% – 300%

Read\Write

1105

DCI

Time

- this is the amount of time that the Opal will DC inject for

1 – 60 seconds

Read\Write