4.3.7. Measurement of current harmonics

WARNING

Before attempting any measurement disconnect all the test leads from the
circuit under test and from the meter's input terminals.

CORRECT

INCORRECT

Fig. 11: harmonic current measurement


1. Select the “

H

A

position.

2. Open the jaws and clamp only one cable. Pay attention to the alignment marks (see

paragraph 4.1.2. and Fig. 11). The instrument displays the Total Harmonic Distortion
value of the input signal. The symbol “THD%” is shown on the display. See chapter 8
for the parameter’s definition.

3. The

↑ and H↓ keys allow the percentage harmonics’ values displaying (from 1

st

to 25

th

order). On the secondary display is shown the order of the harmonic whose percentage
value is displayed on the main display (ex. H3% means third harmonic).

4. Press FUNC key to switch to the absolute harmonics’ values displaying (from 1

st

to

25

th

order). On the secondary display is shown the order of the harmonic whose

absolute value is displayed on the main one (ex. H3 means third harmonic).

5. If the display is difficult to read, press D-H key to hold the measured value. To disable

this function press the D-H key again.

6. If the measurement is being performed in a dark environment, press and hold the

key for 1 second to activate the backlight. It automatically turns OFF after 5 seconds.

EN - 16