Warning – Amprobe ACD-55HPQ Clamp-Meter User Manual

Page 24

Advertising
background image

ACD-55HPQ

6. After about one second “MEASURING“ appears on the display indicating that the

instrument is ready to execute the first measurement.

7. Press the FUNC key, the “MEASURING” symbol will disappear.
8. Disconnect the test lead. The symbol “

2

PH

” appears on the secondary display. The

instrument is now ready to perform the second measurement.

9. Connect the test lead to the second L1 cable (see Fig. 14 2

nd

measurement or Fig. 15,

2

nd

measurement).

10. When an input voltage greater than 80V is detected the buzzer sounds and the

symbols “

PH

” is shown on the main display. Don’t press any key and keep the test

lead connected to L2 phase cable.

WARNING

If the input voltage value is less to 80V instrument doesn’t show “

PH

symbol and its not possible to execute the phase rotation detection.


11. After about one second “MEASURING“ appears indicating the instrument is ready to

execute the second measurement.

12. Press the

FUNC key, the “MEASURING” symbol disappears.

WARNING

If you Wait more than 10 seconds between the first

FUNC key press and

the second, the instrument will display the “

SEC

” message and it’s

necessary to repeat all the measurements from the beginning. Rotate the
selector to any position to escape the function and restart at step 1.


13. If the two test cables belong to the same phase, the instrument displays “

1.1.-.

”,

otherwise it shows “

2.1.3

.” or “

1.2.3

.” This indicates that the two cables belong to two

different phases.

WARNING

• The detected voltage is NOT the phase to neutral voltage, but the

voltage between the conductor and the operator who is holding the
instrument. This value can be lower than the phase to neutral voltage.
DON’T TOUCH THE PHASE CABLE IF YOU AREN’T SURE THAT
ANY VOLTAGE IS PRESENT
.

• If the operator is insulated from the ground (e.g. insulated floors, shoes

with rubber souls, etc.) the instrument may not measure correctly. We
recommend repeating the test at least twice to assure the accuracy of
the obtained result.


EN - 20

Advertising