ProSoft Technology MVI56E-MNETC User Manual
Page 171

MVI56E-MNETC ♦ ControlLogix Platform
Reference
Modbus TCP/IP Client Enhanced Communication Module
User Manual
ProSoft Technology, Inc.
Page 171 of 183
February 3, 2013
4 Select the Requested Packet Interval value for scanning the I/O on the
module. This value represents the minimum frequency that the module will
handle scheduled events. This value should not be set to less than 1
millisecond. The default value is 5 milliseconds. Values between 1 and 10
milliseconds should work with most applications.
5 Save the module. Click OK
to dismiss the dialog box. The Controller
Organization window now displays the module's presence.
6 Copy the User-Defined Data Types from the sample program into your
existing RSLogix 5000 project.
7 Copy the Controller Tags from the sample program into your project.
8 Copy the Ladder Rungs from the sample program into your project.