Guide to the MVI56E-MNETC User Manual
MVI56E-MNETC ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Client Enhanced Communication Module
Page 28 of 183
ProSoft Technology, Inc.
February 3, 2013
Parameter
Value
Comm Format
Select D
ATA
-INT.
Slot
Enter the slot number in the rack where the MVI56E-MNETC
module is located.
Input Assembly Instance
1
Input Size
250
Output Assembly Instance
2
Output Size
248
Configuration Assembly Instance
4
Configuration Size
0
4 Click OK
to confirm. The new module is now visible:
5 Expand the T
ASKS
folder, and then expand the M
AIN
T
ASK
folder.
6 In the M
AIN
P
ROGRAM
folder, double-click to open the M
AIN
R
OUTINE
ladder.