Module Addressing

Modbus Slave Interface Module

User Manual

ProSoft Technology, Inc.

Page 21 of 55

October 27, 2010

4.2

Writing Discrete Outputs

Each word address consists of 16 bits. These bits can be written as discrete

outputs. Word address 40201 corresponds to discrete outputs 3201 to 3216.

40202 corresponds to discrete outputs 3217 to 3232.

((Address - 40001) X 16) + 1 This will give you the Output address 0 of the

word.