1.2

Modbus Specifications

The 3170-MBS product support the following features:
 RTU mode (binary) with CRC-16 error checking
 ASCII 7 and 8-bit modes with LRC error checking
 Accepts broadcast commands from the Master
 Function codes:

1: Read Output Coils (Horizontal addressing only)

2: Read Discrete Inputs (Horizontal addressing only)

3: Read Multiple Holding Registers

4: Read Multiple Input Registers

5: Force (Write) Single Coil (Horizontal addressing only)

6: Preset (Write) Single Holding Register

16: Preset (Write) Multiple Holding Registers

 Pre-assigned Modbus memory map
 Parameters configured via dip switches:

o

Address: 1 to 247

o

Parity: None, Odd or Even

o

Stop Bits: 1 or 2

o

Baud Rate: 1200, 2400, 4800, 9600, 19200, 38400, 62500