1 adapter status word – ProSoft Technology 3170-MBS User Manual

Page 24

Advertising
background image

Status Information

3170-MBS ♦ Flex Platform

User Manual

Modbus Slave Interface Module

Page 24 of 55

ProSoft Technology, Inc.

October 27, 2010

5.1

Adapter Status Word

Address

Bit: 15

14 13 12

11 10 9 8

7

6

5

4

3

2

1

0

40121

Not
Used

I/O
State

Slot
7

Slot
6

Slot
5

Slot
4

Slot
3

Slot
2

Slot
1

Slot 0

The input status word consists of:
 I/O module fault bits - 1 status bit for each slot
 I/O Last state Dip Switch S2-8(See 3170-MBS installation manual)

Bit Description

Bit

Explanation

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

I/O Module Fault

3

This bit is set (1) when an error is detected in slot position 3.

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

I/O Last State

8

= 1 for hold last state = 0 for off

9 to 15

Not used set to 0

The adapter input status word bit descriptions are shown in the following table.