Diagnostics and Troubleshooting

3170-MBS ♦ Flex Platform

User Manual

Modbus Slave Interface Module

Page 30 of 55

ProSoft Technology, Inc.

October 27, 2010

6.1

LED Indicators

The following explains the operation of the LEDs.

LED

Color

Status

Indication

Power

Green

On

Normal state: The module is operating normally, with
communications being detected on the link

Blink

Modbus Communication Timeout: The port has not detected any
communications on the link for over 1 second. If the HOLD LAST

STATE dip switch is not set, the Input and Output images will be

forced to zero(0).

FLEX Backplane Communications Fail: The communication
adapter either does not detect any I/O modules plugged into the

backplane, or the backplane communications have failed.

Transmit Green

Blink

The Modbus port is transmitting data.

Receive Green

Blink

The Modbus port is receiving data. LED flashes on any character

activity, valid or invalid.

COM
ERR

Amber

Off

Normal State: When the error LED is off and the related port is
actively transferring data, there are no communication errors

Blink

Periodic communication errors are occurring during data

communications. Error conditions that cause LED to blink include:


Bad Function Code



Invalid Register Address in command



Invalid Count value in command



Insufficient Characters in Modbus Packet



Checksum Error detected in packet

FLEX Backplane Communications Fail: The communication
adapter either does not detect any I/O modules plugged into the

backplane, or the backplane communications have failed

On

This LED will stay on under several conditions:
Configuration Error
Recurring communication error