3.4.5 Configure Ethernet Settings
Use this procedure to configure the Ethernet settings for your module. You must
assign an IP address, Subnet Mask and you may also want to assign a Default
Gateway Address if one exists on your network. After you complete this step, you
can connect to the gateway with an Ethernet cable.
1 Determine the network settings for your module, with the help of your network
administrator if necessary. You will need the following information:
o
IP address (fixed IP required) _____ . _____ . _____ . _____
o
Subnet mask
_____ . _____ . _____ . _____
o
Gateway address
_____ . _____ . _____ . _____
2 Click [+] next to the gateway name to expand the tree for the 5204SE-MNET-
PDPMV1 module. Click [+] next to the C
OMMON
N
ET
option to reach the
E
THERNET
C
ONFIGURATION
.