Installation, Cb a – Enviro EF THERMO 28 User Manual

Page 12

Advertising
background image

Floor Protection

C

B

A

Maintain these clearances to combustibles.

A) Side wall to unit

6 inches

(153 mm)

B) Back wall to unit

1 inch

( 25 mm)

C) Adjacent wall to corner of unit

1 inch

( 25 mm)

- Mantle (Hearth Mount)

8 inches

(203 mm)

Installation

C

LEARANCES

TO

C

OMBUSTIBLES

:

A

LCOVE

C

LEARANCES

:

This unit may be installed in an alcove. Maintain

clearances to combustibles.

Minimum Alcove width 36 inches ( 914 mm)

Minimum alcove height 48 inches (1220 mm)

Maximum alcove depth 30 inches ( 762 mm)

Install vent at clearances specified by

the vent manufacturer.

30

" (

75

cm

)

48"

(120cm)

36" (90cm)

Figure 15

Figure 14

12

This unit can be installed on a combustible floor

due to the built in pedestal hearth pad (for example

linoleum, hardwood flooring). If combustible

flooring is underneath the unit 6 inches (153 mm)

on either side and to the front must be protected

by non-combustible material. If this unit is to be

installed onto a carpeted surface, a hearth pad

must be used for stability.

NOTE: These dimensions are minimum clearances

but it is recommended that you ensure sufficient

room (20” [508 mm]) on either side) for servicing,

routine cleaning and maintenance.

Do not block any of the air intake grills.