Installation – Enviro EF THERMO 28 User Manual

Page 18

Advertising
background image

Installation

T

HERMOSTAT

I

NSTALLED

:

If the unit has been placed in the HI / LOW mode, the unit will be taken to a low or idle setting when the

thermostat is not calling for heat. When the thermostat calls for heat, the unit will go to the setting that

is displayed on the control board Heat Indicator. If the heating load is not great enough when the stove

is on low, the high limit switch will turn the stove off and the switch will have to be manually reset. To

reset the high limit switch, remove the right cabinet side. The switch is found behind the control panel.

Avoid setting off the high limit switch.

M

OBILE

H

OME

I

NSTALLATION

:

•Secure the heater to the floor using the two bolt holes supplied in the pedestal.

CAUTION: THE STRUCTURAL INTEGRITY OF THE MANUFACTURED HOME FLOOR, WALL,

AND CEILING/ROOF MUST BE MAINTAINED.

•Ensure the unit is electrically grounded to the chassis of your home (permanently).

•Do not install in a room where people sleep.

•Outside fresh air is mandatory when installing into airtight homes or manufactured homes.

F

RESH

-A

IR

C

ONNECTIONS

:

A) HI / LOW: When the

jumper is placed on

only one of the J9 pins,

then the control board

is in a HI / LOW mode

of thermostat operation

(factory setting).

B) ON / OFF: If

both pins of J9 are

jumped (covered), the

control board is in an

ON / OFF mode of

thermostat operation .

Remove jumper wire and install thermostat

wires here

Figure 21

NOTE: Fresh air is mandatory on all units installed in “Mobile

Homes” as well as in “Air Tight” homes.

When connecting to an outside fresh-air source, do not use plastic,

combustible pipe. Only 2” (5 cm) ID steel, aluminum or copper pipe

should be used. It is recommended, when you are installing a fresh-air

system, to keep the number of bends in the pipe to a minimum.

Figure 22

This control board can be placed into two different

modes: When the jumper J9 is not jumped

then the control board is in a HI / LOW mode

operation. If the control board is placed with J9

jumped then the control board is in a ON / OFF

mode of operation. In the ON /OFF thermostat

mode, the unit will shut OFF when the thermostat

is not calling for heat. When the thermostat calls

for heat, the unit will go through an ignition

sequence once again and relight.

1. Install the wall thermostat in a location that

is not to close too the unit but will effectively

heat the desired area.

2. Install a 12 or 24 Volt Thermostat using an 18 x

2 gauge wire from the unit to the thermostat.

18

Advertising