NS SPLIT INSTALLATION MANUAL

Service valves have been provided inside the unit for connecting the discharge gas line to a water heating heat recov-

ery unit (see figure 5). To make the connections, close the service valves inside the unit by turning clockwise. Using a

recovery canister connect to either of the schrader ports on the DSH service valves and recover the small amount of refrig-

erant trapped inside of the U-tube.

Prior to brazing ensure that all refrigerant has been removed from U-tube. Once

the refrigerant is removed, it is recommended that the tube be cut at the “U” to remove any excess oil that may be trapped.

(This will also allow for easier removal of the tubing with a torch, since each section can be removed independently).

Ser-

vice valves must be protected to prevent overheating. Unbraze the 1/2-inch O.D. U-tube and run tubing from the left

hand service valve to the inlet of the heat recovery unit and from the outlet of the heat recovery unit to the right hand of the

service valve. Typically the one way discharge line length should be limited to 25-30 feet and line size must be increased

depending on unit size and length of run. Follow the instructions supplied with the heat recovery unit for mounting location,

water piping, and start up. A typical installation is shown below.

IMPORTANT - Reopen discharge line service valves before starting up unit, but only after leak checking,

purging, and evacuating new discharge line.

To

Compressor

Heat Recovery

Unit “In”

From

Heat Recovery

Unit “Out” to

Reversing

Valve

Insulated Line set

With UV Paint

To Air handler

Add-on

Hot Water

Generator with

Internal Pump

Cold

Drain Valve

Pipe Tee

Hot

Venting

Waste Valve or

Vent Coupling

Line set

To Hot Water

Generator

P/T Relief

Valve

Figure 5: Service Valves for Heat Recovery Unit Connections

Figure 6: Typical Hot Water Piping Layout

SIZE

1/2” OD

5/8” OD

3/4” OD

026 - 038

Up to 9 ft.

Up to 25 ft.

Up to 30 ft.

049

Up to 5 ft.

Up to 13 ft.

Up to 30 ft.

064

N/A

Up to 9 ft.

Up to 25 ft.

072

N/A

Up to 6 ft.

Up to 20 ft.

Maximum One-Way Line Length

Heat Recovery Unit for Domestic Hot Water