Eaton Electrical 0800-2000 User Manual

Page 15

Advertising
background image

14

Menu 2: System Status (continued)

Menu 3: System Status Info

By pressing

¿ while displaying this parameter, you can start a User

Test alarm to make sure the FERRUPS alarms properly or to test
alarm contacts at the DB9 communication port. By pressing

¿ again,

you can stop the User Test alarm.

This parameter shows the results of the last system test.

Not

applicable.

List

None

No change

allowed.

2 10
Test Alarm
testalarm

2 9
Test Results
tresults

This parameter provides control of the system test.

List

User

2 8
Test Control
testcon

This parameter shows why the UPS transferred from AC input
power to battery power. (Possible causes are system/battery test,
brownout, line loss, manual, frequency, or reset.)

List

No change

allowed.

2 7
Transfer Code
xfercode

This is a hexadecimal alarm status value used by CheckUPS
software.

0-0XFFFF

No change

allowed.

Explanation

Range

Password to

Change

Item and Sample

Display

2 6

Show Alarm Code #2

almcode2 0000 hex

Watts out. The total real power your equipment is drawing from the
FERRUPS.

Volt-amperes out. The total apparent power your equipment is
drawing from the FERRUPS. This value is based on parameter 3 4
multiplied by parameter 3 6.

The current your equipment is drawing from the FERRUPS.

The current the FERRUPS is drawing from the AC input source.

Not

applicable.

Not

applicable.

1.0-900.0

1.0-900.0

No change

allowed.

No change

allowed.

No change

allowed.

No change

allowed.

3 9
Watts Out
watts 1.4 kW

3 8
VA Out
vaout 2 KVA

3 7
AC Output Current
aciout 16.7

3 6
AC Input Current
aciin 16.7 A

The voltage the FERRUPS is providing to your equipment.

65-300

No change

allowed.

3 5
AC Output Volts
acvout 120 V

The input voltage the FERRUPS is receiving. When this value drops
below the brownout voltage, the FERRUPS switches to battery
power.

65-300

No change

allowed.

3 4
AC Input Volts
acvin 120 V

Year.

Date. The FERRUPS uses this date to record alarms and battery
power operation in its logs. (See

Section 506

.)

1994-2130

0101-1231

Time (displayed in 24-hour time). The FERRUPS uses this time to
record alarms and battery power operation in its logs. (See

Section

506

.)

0001-2459

User

3 1
Unit Time
time 01:15

User

User

Explanation

Range

Password to

Change

Item and Sample

Display

3 3
Unit Year
year 1998

3 2
Unit Date
date = 07/08