Honeywell Q674F User Manual

Page 3

Advertising
background image

3

69-0435—10

Fig. 2—Installation of Q674 Subbase on wall.

WIRES THROUGH
WALL OPENING

WALL

WALL
ANCHORS
(2)

SUBBASE

MOUNTING
HOLES

MOUNTING
SCREWS (2)

M926

Fig. 3—Subbase components and leveling
procedure.

SPIRIT LEVEL

MOUNTING HOLES (2)

M927

TOP MOUNTING HOLES (2)

WIRING
TERMINAL

THERMOSTAT
CABLE OPENING

TO SPRING FINGER CONTACTS
ON THE THERMOSTAT
(UP TO 12)

POST (2) FOR
MOUNTING
THERMOSTAT

IMPORTANT: Use 18 gauge, color-coded thermostat

cable for proper wiring.

3. Pull wires through the cover plate (if used) and

sub-base cable opening. See Fig. 3. Take care that wires
do not fall back into the wall opening.

4. Secure the cover plate (if used) and subbase with the

screws provided. Do not fully tighten the subbase screws.

5. Level the subbase using a spirit level, as shown in

Fig. 3, and firmly tighten subbase mounting screws.
The subbase mounting holes provide for minor out-of-
level adjustments.

IMPORTANT: An incorrectly leveled subbase will cause

the temperature control to deviate from set point.

WIRING THE SUBBASE

All wiring must comply with local electrical codes and

ordinances. Follow equipment manufacturer wiring instruc-
tions when available. To wire subbase, proceed as follows:

Fig. 4—Wiring Connections.

FOR STRAIGHT
INSERTION–
STRIP 5/16 in. [8 mm]

FOR WRAPAROUND–
STRIP 7/16 in. [11 mm]

SUBBASE TERMINAL SCREW

M928

BARRIER

1. Connect the system wires to the subbase as shown

in Figs. 5-11. A letter code located near each terminal is
for identification. The terminal barrier permits straight or
conventional wraparound wiring connection. See Fig. 4.

2. Firmly tighten each terminal screw.
3. Fit wires as close as possible to the subbase. Push

excess wire back into the hole.

4. Plug hole with nonflammable insulation to pre-

vent drafts from affecting the thermostat.