Technical specifications, Quickspecs – HP SL160Z User Manual

Page 31

Advertising
background image

System Unit

Dimensions (H x W x D)
(with bezel)

3.46 x 17.64 x 28.1 in (8.79 x 44.80 x 71.37 cm)

Weight
(approximate)

Maximum
(all hard drives, power
supplies, and processors
installed)

53.7 lb (24.35 kg)

Input Requirements
(per power supply)

Rated Line Voltage

90 to 132 VAC
180 to 264 VAC

Rated Input Current

5. 8 Amps (at 100 VAC) to 2.9 Amps (at 200
VAC)

Rated Input Frequency

47 to 63 Hz

BTU Rating

Rated Input Power

570W (at 100 VAC)
565W (at 200 VAC)

Maximum

-500W 1940 BTU / hr (at 100 VAC), 1920
BTU/hr (at 200 VAC)
460W - 1773 BTU / hr (at 120 VAC), 1715 (at
240 VAC)
750W - 2892 BTU / hr (at 120 VAC), 2797 (at
240 VAC)

Power Specifications

To review typical system power ratings use the HP Power Advisor which
is available via the online tool located at URL:

www.hp.com/go/proliant-

energy-efficient

Power Supply Output
(per power supply)

Rated Steady-State
Power

500 Watts (at 100 VAC),
500 Watts (at 200 VAC)

Maximum Peak Power
(See Power
Specifications Tables)

500Watts (at 100 VAC),
500 Watts (at 200 VAC)

System Inlet
Temperature

Operating

10° to 35°C (50° to 95°F) at sea level with an
altitude derating of 1.0°C per every 305 m
(1.8°F per every 1000 ft) above sea level to a
maximum of 3050 m (10,000 ft), no direct
sustained sunlight. Maximum rate of change
is 10°C/hr (18°F/hr). The upper limit may be
limited by the type and number of options
installed.
System performance may be reduced if
operating with a fan fault or above 30°C
(86°F).

Non-operating

-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).

Relative Humidity
(non-condensing)

Operating

10 to 90% relative humidity (Rh), 28°C
(82.4°F) maximum wet bulb temperature, non-
condensing.

Non-operating

-30° to 60°C (-22° to 140°F). Maximum rate of
change is 20°C/hr (36°F/hr).

Altitude

Operating

3050 m (10,000 ft). This value may be limited
by the type and number of options installed.
Maximum allowable altitude change rate is
457 m/min (1500 ft/min).

Non-operating

9144 m (30,000 ft). Maximum allowable
altitude change rate is 457 m/min (1500
ft/min).

Acoustic Noise

Listed are the declared A-Weighted sound power levels (LWAd) and

QuickSpecs

HP ProLiant SL160z Generation 6 (G6)

Technical Specifications

DA - 13385 Worldwide QuickSpecs — Version 1 — 6.15.2009