TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT

63-2635—03

22

TROUBLESHOOTING (TABLE 11)

Table 11. Troubleshooting.

Symptom

Possible Cause

Action

Display does not come on.

Thermostat is not being powered.

Check for 24 Vac between C and Rc.

Check that AAA batteries are installed correctly

and are good.

Temperature settings do not

change.

The upper or lower temperature limits were

reached.

Check temperature setpoints.

Check ISU 0600 and 0610; modify as needed.

The keypad is fully locked.

Check ISU 0670 to change keypad locked

options.

Heating or cooling does not come

on.

Thermostat minimum off-time is activated. Wait up to five minutes for the system to respond.
System selection is not set to Heat or Cool. Set system Selection to correct position.
System type Selection is incorrect.

Check ISU 0170 and make sure correct System

type is chosen.

Thermostat is calling for Heat

(Heat on) or Cool (Cool on) but

no heating or cooling is running.

Heating or cooling equipment is not

operating.

Check wiring.

Check ISU 0170 and make sure correct system

type is chosen.

Verify operation of equipment in System Test

mode.

Heat does not turn on (Heat On is

solid in the display).

Heating equipment failure.

Check for 24 Vac at the equipment on the

secondary side of the transformer between power

and common. If voltage is not present, check the

heating equipment to find the cause of the

problem.

Check for 24 Vac between the heat terminal (W)

and transformer common. If 24 Vac is present, the

thermostat is functional. Check the heating

equipment to find the cause of the problem.

Loose or broken wire connection between

thermostat and heating equipment.

Check for 24 Vac between the heat terminal (W)

and transformer common. If voltage is not

present, check wire connection (loose or broken)

between the thermostat and the heating

equipment.

Cooling does not turn on (Cool

On is solid in the display).

Cooling equipment failure.

Check for 24 Vac at the equipment on the

secondary side of the transformer between power

and common. If voltage is not present, check the

cooling equipment to find the cause of the

problem.

Check for 24 Vac between the cool terminal (Y)

and transformer common. If 24 Vac is present, the

thermostat is functional. Check the cooling

equipment to find the cause of the problem.

Loose or broken wire connection between

thermostat and cooling equipment.

Check for 24 Vac between the cool terminal (Y)

and transformer common. If voltage is not

present, check the wire connection (loose or

broken) between the thermostat and the cooling

equipment.

Fan does not turn on in a call for

heat (electric furnace).

Fan Control in Heating is set to Gas or Oil

Furnace (Setting 0180).

Set Fan Control in Heating to Electric Furnace

(Setting 0180).

Heat pump puts out cool air in the

heat mode and warm air in the

cool mode.

Changeover Valve (ISU 0190) is not

configured to match the changeover

required by the installed heat pump.

Set Changeover Valve (ISU 0190) to match the

changeover required by the installed heat pump.

Both the heating and cooling

equipment are running at the

same time.

The heating equipment is not a heat pump

but the System Type (ISU 0170) is set to

Heat Pump.

Set System Type (ISU 0170) to match the

installed heating and/or cooling equipment.

Heating and cooling wires are shorted

together.

Separate the shorted heating and cooling wires.