SECTION 7 − OPERATING AUXILIARY EQUIPMENT

7-1. Standard Receptacles

244 029-A / 281 080-A

!

If unit does not have GFCI recep-

tacles, use GFCI-protected exten-

sion cord.

.

Generator power decreases as weld
current increases.

Set Fine Control R1 at 10 for full gen-

erator power.

1

240 V 50 A AC Receptacle RC1

RC1 supplies 60 Hz single-phase power

at weld/power speed. Maximum output is

11 kVA/kW.
2

120 V 20 A AC Duplex Receptacle

RC2

3

120 V 20 A AC Duplex Receptacle

RC3

RC2 and RC3 supply 60 Hz single-phase

power at weld/power speed. Maximum

output from RC2 or RC3 is 2.4 kVA/kW.
4

240 V 50 A AC Receptacle RC5

RC5 supplies 60 Hz single-phase power

at weld/power speed. Maximum output is

11 kVA/kW.

5

Supplementary Protector CB1

CB1 protects receptacles RC1, RC2,

RC3, and RC5 from overload. If CB1

opens, the receptacles do not work. Place

switch in On position to reset.
6

Supplementary Protector CB2

7

Supplementary Protector CB3

CB2 protects RC2 and CB3 protects RC3

from overload. If a supplementary protec-

tor opens, the receptacle does not work.

.

Press button to reset. If supplementa-
ry protector continues to open, con-

tact Factory Authorized Service

Agent.

GFCI Receptacle Option
8

120 V 20 A AC GFCI Receptacles

GFCI-2 and GFCI-3

GFCI2 and GFCI3 supply 60 Hz single-

phase power at weld/power speed. Maxi-

mum output from GFCI-2 or GFCI-3 is 2.4

kVA/kW. Circuit protection is the same as

standard receptacles.

If a ground fault is detected, the GFCI Re-

set button pops out and the circuit opens

to disconnect the faulty equipment. Check

for damaged tools, cords, plugs, etc. con-

nected to the receptacle. Press button to

reset receptacle and resume operation.

!

Power is still present at the 240 volt

receptacle when only one circuit

breaker trips.

Unplug power cord before attempt-

ing to service accessories or tools.

.

At least once a month, run engine at
weld/power speed and press Test but-

ton to verify GFCI is working properly.

Combined output of all receptacles limited

to the rating of the generator.
Example: If 20 A is drawn from each 120

V duplex receptacle, only 26 A is available

at the 240V receptacle:
2 x (120 V x 20 A) + (240 V x 26 A) = 11.0

kVA/kW