CONTROL & FEATURES

i-Monitor Low Battery Message

i-Monitor System Error Messages

OVERLOAD INDICATOR LIGHT

ERROR MESSAGE
(Example: E-01)

If the generator has a system malfunction, it will show an error
message on the i-Monitor display. During remote control operation, an
E-01 error message may display if the starter button is pressed for
more than 10 seconds. With an E-01 error message, the engine will
stay running and the electrical output may stay constant.
Normal remote control operation will be restored after the E-01 error
message clears. If the E-01 error message will not clear or if any other
error message displays, contact an authorized Honda generator dealer.

If the engine switch is turned to the START position and ‘‘batt’’ is
shown on the i-Monitor display, the battery voltage is too low to
operate the engine’s electric starter. Use the recoil starter to start the
generator. Have the battery recharged and checked (see page

).

58

07/12/21 14:01:33 31Z11710_022