Hearth and Home Technologies HST-48D User Manual

Page 20

Advertising
background image

20

47 in.

[1194 mm]

width of fireplace

42 in.

[1067 mm]

fireplace opening

9 3/4 in.

[248 mm]

12 in.

[305 mm]

12 in.

[305 mm]

11 3/8 in.

[289 mm]

FLUSH
FRONT

4 in.

[102 mm]

BRICK

FRONT

50° angle

39° angle

Gridlines at 1 in. scale

D. Frame the Fireplace

Figure 6.4 shows typical framing using combustible materials (2x4 lumber shown).

• Observe all required air space clearances to combustible materials as shown in Figure 6.2.
• Framing across the top of fi replace must be above top standoffs.

You must maintain

2 in. (51 mm) min. air space

clearance from the

chimney to the

enclosure.

27 in.

(686 mm)

Note: Fireplace

Header cannot be

positioned until after

the fireplace assembly

is in place.

12 in. (305 mm) max.

48 in.

(1219 mm)

Figure 6.4 Framing the Fireplace

C. Sidewalls/Surrounds

• Adjacent combustible sidewalls must be located a minimum of 12 in. (305 mm) from the fi replace opening.
• Combustible and noncombustible mantel legs, surrounds and stub walls may be constructed within the gridded area,

Figure 6.3.

Figure 6.3 Mantel Leg or Wall Projections (Acceptable on both sides of fi replace)

Heat & Glo • HST-48D US-CAN • 4012-040 • Rev F • 11/08