A. Chimney Requirements

Measure vertical distances from the base of the fi replace
as shown in Figure 8.2.

d & g

Ceiling Firestop

h

i

58-7/8 in.

(1495 mm)

Effective

Height

a,b,c,f

11-10 in. (279-254 mm)

adapter required in

Canada.

Figure 8.2 Chimney Requirements (refer to list in Sect. 5.A.)

Table 8.1

ft

meters

a. Minimum overall straight height

14.0

4.27

b. Minimum height with offset/return

16.5

5.03

c. Maximum height

90.0

27.43

d. Maximum chimney length between an offset and

return

20.0

6.1

e. Maximum distance between chimney stabilizers

35.0

10.67

f. Double offset/return minimum height

22.0

6.71

g. Maximum unsupported chimney length between the

offset and return

6.0

1.83

h. Maximum unsupported chimney height above the

fi replace

35.0

10.67

i. Maximum unsupported chimney above roof

6.0

1.83

WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and fi re.

Determine the chimney components needed to complete
your particular installation:

• Measure the total vertical height of the fireplace

installation from the base of the fi replace assembly to
the approximate location of the bottom of the termination
cap.

• Subtract the effective height of the fi replace assembly

(see Figure 8.2) from the total vertical height to determine
the overall height of the chimney installation.

• Create a schematic for your application similar to Figure

8.2 showing components required (referring to Table
8.1). Figure 8.1 identifi es those components and where
used.

• Install a ceiling fi restop whenever the chimney penetrates

a fl oor/ceiling.

NOTICE:

A maximum of two pairs of offsets and returns

may be used.

CAUTION! Risk of Fire and/or Asphyxiation! DO

NOT connect this fi replace to a chimney fl ue servicing
another appliance. DO NOT connect to any air distribu-
tion duct or system. These actions could cause over-
heating/fi re in the chimney fl ue, or release of exhaust
fumes into the living areas.

Heat & Glo • HST-48D US-CAN • 4012-040 • Rev F • 11/08

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

US

Canada ONLY

Chimney Stabilizer

SL11

SL4

4-3/4

121

Ceiling Firestops

FS538

FS538

0

0

FS540

FS540

0

0

Offsets/Returns

SL1130

SL430

14-1/2

368

Roof Flashing

RF570

RF570

0

0

RF571

RF571

0

0

Chimney Sections*

SL1106

SL406

4-3/4

121

SL1112

SL412

10-3/4

273

SL1118

SL418

16-3/4

425

SL1136

SL436

34-3/4

883

SL1148

SL448

46-3/4

1187

n/a

SLA10

16-3/4

425

* Dimensions refl ect effective height.