E. Combustible Mantel

• See Figure 11.4.
• A combustible mantel may be positioned no lower

than 12 in. (305 mm) above the top of the fi replace
opening.

• A combustible mantel may have a maximum depth of

12 in. (305 mm).

• Combustible trim and materials cannot be placed within

6 in. (152 mm) of the fi replace opening (top or sides).

• Combustible materials projecting more than 1-1/2 in.

(38 mm) shall not be placed within 12 in. (305 mm) from
the top of the fi replace opening.

• Combustible trim must not cover the metal surfaces of

the fi replace.

• Mantel clearance is in accordance with Section 7-3.3.3

of ANSI/NFPA211.

12 in.
(305 mm)
max.

12 in.
(305 mm)
min.

Gas

Knockout

Figure 11.4 Clearances to Mantels or other Combustibles above
Fireplace

F. Sidewalls/Surrounds

• Adjacent combustible sidewalls must be located

a minimum of 12 in. (305 mm) from the fireplace
opening.

• Combustible or non-combustible mantel legs, surrounds

and stub walls may be constructed per Figure 11.5.

47 in.

[1194 mm]

width of fireplace

42 in.

[1067 mm]

fireplace opening

9 3/4 in.

[248 mm]

12 in.

[305 mm]

12 in.

[305 mm]

11 3/8 in.

[289 mm]

FLUSH
FRONT

4 in.

[102 mm]

BRICK

FRONT

50° angle

39° angle

Gridlines at 1 in. scale

Figure 11.5 Mantel Leg or Wall Projections (acceptable on both sides of opening)

Heat & Glo • HST-48D US-CAN • 4012-040 • Rev F • 11/08