OM-314 Page 11

2-5.

Selecting A Location

1

Rating Label

Use rating label to determine input
power needs. Label located on front
panel.

2

Line Disconnect Device

Locate unit near correct input pow-
er supply.

Y

Special installation may be
required where gasoline or
volatile liquids are present –
see NEC Article 511 or CEC
Section 20.

2

18 in

(460 mm)

18 in

(460 mm)

Movement

Location And Airflow

1

Y

Do not move or operate unit
where it could tip.

Tipping

loc_1 3/96 / Ref. ST-111 900-D

2-6.

Weld Cable Sizes

Total Cable (Copper) Length In Weld Circuit Not Exceeding

100 ft (30 m) Or Less

150 ft

(45 m)

200 ft

(60 m)

250 ft

(70 m)

300 ft

(90 m)

350 ft

(105 m)

400 ft

(120 m)

Welding

Amperes

10 To 60%

Duty Cycle

60 Thru 100%

Duty Cycle

10 Thru 100% Duty Cycle

100

4

4

4

3

2

1

1/0

1/0

150

3

3

2

1

1/0

2/0

3/0

3/0

200

3

2

1

1/0

2/0

3/0

4/0

4/0

250

2

1

1/0

2/0

3/0

4/0

2-2/0

2-2/0

300

1

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-3/0

350

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-3/0

2-4/0

400

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-4/0

2-4/0

*Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.