8. electrical service guide – Hobart Welding Products CYBERSTICK OM-314 User Manual

Page 17

Advertising
background image

OM-314 Page 13

2-8.

Electrical Service Guide

60 Hertz Models

With Power Factor Correction

Without Power Factor Correction

Input Voltage

200

230

460

575

200

230

460

575

Input Amperes At Rated Output

78

68

34

27

103

90

45

36

Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes

125

100

50

40

150

125

70

50

Min Input Conductor Size In AWG/Kcmil

8

8

12

14

6

8

10

12

Max Recommended Input Conductor Length
In Feet (Meters)

61 (19)

80 (25)

131

(40)

133

(40)

87 (27)

77 (23)

208

(64)

200

(61)

Min Grounding Conductor Size In AWG/Kcmil

8

8

12

14

6

8

10

12

Reference: 1993 National Electrical Code (NEC)

S-0092-J

50 Hertz Models

With Power Factor Correction

Without Power Factor

Correction

Input Voltage

220

260

380

440

520

220

380

440

Input Amperes At Rated Output

68

57

39

34

29

84

49

42

Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes

100

90

60

50

45

125

70

60

Min Input Conductor Size In AWG/Kcmil

8

8

10

12

12

8

10

10

Max Recommended Input Conductor Length
In Feet (Meters)

79 (24)

110 (33)

157

(48)

128

(39)

179

(55)

76 (23)

153

(47)

205

(63)

Min Grounding Conductor Size In AWG/Kcmil

8

8

10

12

12

8

10

10

Reference: 1993 National Electrical Code (NEC)

S-0092-J