Hearth and Home Technologies Heat & Glo SL-550TR-D User Manual

Page 41

Advertising
background image

41

Heat & Glo • SL-550 / 750 / 950TR-D • InD • 2044-985 Rev. M • 10/06

E. Junction Box Installation

F. Wall Switch Installation for Fan (Optional)

Figure 10.6 Junction Box Wired to Wall Switch

If the box is being wired to a wall mounted
switch for use with a fan (See Figure 10.6):

• The power supply for the appliance must

be brought into a switch box.

• The power can then be supplied from

the switch box to the appliance using a
minimum of 14-3 with ground wire.

• At the switch box connect the black (hot)

wire and red (switch leg) wire to the wall
switch as shown.

• At the appliance connect the black (hot),

white (neutral) and green (ground) wires
to the junction box as shown.

• Add a 1/4 inch insulated female connector

to the red (switch leg) wire, route it through
the knockout in the face of the junction
box, and connect to the top fan switch
connector (1/4 inch male) as shown.

If the box is being wired from the appliance:
• Remove the screw attaching the junction

box to the outer shell, rotate the junction box
inward to disengage it from the outer shell
(see Figure 10.5).

• Pull the electrical wires from outside the

appliance through this opening into the valve
compartment.

• Loosen the two screws on the Romex

connector (not included with unit), feed the
necessary length of wire through the connector
and tighten the screws.

• Make all necessary wire connections to the

receptacle and assemble the receptacle and
cover to the junction box.

WHT

WHT

BLK

BLK

GRN wire
inside box

Copper
ground attached
to GRN screw with
GRN wire

14/2WG

Cover Plate
outside firebox

Romex
Connector

Figure 10.5 Junction Box Detail

Red

Red

Black

Black

Green

Green

White

White

Red

Black

Green

White

SWITCH BOX

JUNCTION BOX

POWER

SUPPLY WIRES

SWITCH

MINIMUM 14-3 AWG

WITH GROUND

NOTE: Do NOT wire
110VAC to wall switch.