Installation manual for outdoor unit, Heat pump model/cooling only model, Installation of outdoor unit – haier AU142AFBIA User Manual

Page 13: Warning

Advertising
background image

12

INSTALLATION MANUAL FOR OUTDOOR UNIT

Edging

(2) Installation where the area with strong winds.

Install the unit so that the air outlet section of the unit must NOT be
faced toward wind direction.

(1) Open space requirement around the unit

2. Selection of the place of installation

1. Accessories

"Edging" for protection of electric wires from an
opening edge.

Select the place of installation satisfying the following conditions and, at the same time, obtain
a consent from the client or user.

Place where air circulates.
Place free from heat radiation from other heat sources.
Place where drain water may be discharged.
Place where noise and hot air may not disturb the neighborhood.
Place where there is not heavy snowfall in the winter time.
Place where obstacles do not exist near the air inlet and air outlet .
Place where the air outlet may not be exposed to a strong wind.
Place surrounded at four sides are not suitable for installation. A 1m or more of overhead
space is needed for the unit.
Mount guide-louvers to place where short-circuit is a possibility.
When installing several units, secure sufficient suction space to avoid short circuiting.

<Heat Pump model/Cooling Only model >

WARNING

BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION.

FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH,

EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE. BE SURE TO READ INSTALLATION

MANUAL FOR INDOOR UNIT WITH THIS MANUAL.

Wind direction

NO

Concrete foundation

Foundation anchor

Note (1) Give enough room for the concrete

foundation to fix by anchor bolts.

(a)

Note (1) Place the concrete foundation deep enough.

Install the unit so that the angle of inclination must be less than 3 degrees.

3. Installation of outdoor unit

Fix the unit in a proper way according to the condition of a place where it is installed by referring to the following .

(1) Installation

L

2

L

3

L

1

500

(Servicing
space)

Air outlet

Air inlet

Air
inlet

Unit: mm

Case

Distance

I

II

III

open

open

open

500

150

150

300

300

0

L

1

L

2

L

3

Anchor bolt

To fix by bolts

Anchor bolt

Concrete foundation

Unit

Unit

Concrete foundation

Advertising
This manual is related to the following products: