INSTALLATION MANUAL FOR INDOOR UNIT

20

Warning

!

During installation, if refrigerant leakage occurs, please immediately take ventilation
measure. If the refrigerant gas meet the fire, it may generate poisonous gas.
After finishing installation work, please make sure there is no refrigerant leakage.
If the leaked refrigerant gas meet heater and oven, etc. fire sources, it may generate
poisonous.

Depenbing on the outdoor unit.For details,please refer to the operation manual attached

with outdoor unit.

Material and dimension of connection pipe

The permitted length and fall of connection pipe

Material of connection pipe and thermal insulation

Foam polyethylene pipe, thickness over 10mm

Stiff PVC pipe VP 20mm (inside diameter)

Material of connection pipe

Material of thermal insulation

Perform with two spanners

When performing the connection work of flare nut, connect all

the refrigerant pipe.

When connecting the connection pipe of indoor unit, must

use two spanners to perform.

For the installation torque, please refer the following Table.

Connection of refrigerant pipe

Material of
connection pipe

Gas side

Liquid side

Dimension of
connection pipe

15.88

9.52

Phosphorus oxidized copper seamless pipe
(TP2) for air conditioner

External diameter of
connection pipe (mm)

Installation torque (N.m)

Add to installation torque (N.m)

9.52

24.5(2.5kgf.m)

29.4(3.0kgf.m)

15.88

78.4(8.0kgf.m)

98.0(10.0kgf.m)

Confirm drainage

Perform test run to insure the condition of drainage, the connection part of the connection

should not leak water. The confirmation must be performed even if install in winter.