WARNING

Fire Risk

Explosion Risk

• Gas build-up during line purge may

ignite.

• Purge should be performed by qualified

technician.

• Ensure adequate ventilation.

• Ensure there are no ignition sources such

as sparks or open flames.

C. Gas Pressure

Proper input pressures are required for optimum appliance

performance. Gas line sizing requirements need to be made

following

NFPA51.

Fire Risk

Explosion Risk
High pressure will damage valve.

• Disconnect gas supply piping BEFORE

pressure testing gas line at test pressures

above 1/2 psig.

• Close the manual shutoff valve BEFORE

pressure testing gas line at test pressures

equal to or less than 1/2 psig.

WARNING

High Altitude Derate
In

the USA, input BTU shall be derated 4% (one orifice size)

per 1000 feet for altitudes above 2000 feet. In Canada, input

BTU shall be derated 10% (two orifice sizes) at altitudes

from 2000-4500 feet.

• Gas Supply Pressure: Minimum inlet gas supply pressure

must be 4.5 in. W.C. for natural gas or 11 in. W.C. for LP

gas for the purpose of input adjustment. Maximum inlet

gas pressure must not exceed 7.0 in. W.C. for natural

gas or 13 in. W.C. for LP gas. The gas line supplying the

appliance must be sufficient size to furnish the appropriate

supply pressure to the appliance while operating in the

“High” setting. (Minimum line ID of 1/2 in. required if the

line is longer than 20 ft.).

• Gas Line Pressure Test: Perform pressure test according

to state and local code (if pressure exceeds 1/2 in. psi [3.5

kPa]) before appliance is connected. Be sure to release

air pressure from the gas line before connection is made

to the appliance. Excessive pressure will damage the gas

control and may cause a gas leak.

• Gas Leak Test: Make sure the gas connections are tight.

Turn on the gas and coat each joint with a non-corrosive

gas leak check solution. Air bubbles will form indicating

any leaks. DO NOT USE A FLAME OR ANY TYPE OF

IGNITION SOURCE TO CHECK FOR LEAKS. All leaks

must be corrected before proceeding with installation.

• The appliance must only be installed in a solid-fuel burning

fireplace with the flue damper clamped open.

• The minimum permanent free opening (in square inches)

that must be provided by the fireplace chimney or damper

to vent the flue gases is provided in Table 1. If the free

opening is smaller than the specified area, do not use this

appliance.

• The damper must be removed or fixed in a manner in

which will secure it open. Some jurisdictions require the

damper to be removed or permanently welded fully open.

Check with state and local codes.

• Be sure that the chimney is completely unobstructed to

ensure proper ventilation of flue gases including carbon

monoxide (CO).CO (a poisonous gas) is tasteless,

odorless, colorless and undetectable without proper

equipment.

WARNING

CHECK FOR GAS LEAKS

Fire Risk

Explosion Risk

Asphyxiation Risk

• Check all fittings and connections.

• Do not use open flame.

• After the gas line installation is complete,

all connections must be tightened and

checked for leaks with a commercially

available, non-corrosive leak check

solution. Be sure to rinse off all leak check

solution following testing.

Fittings and connections may have loosened

during shipping and handling.

WARNING

Fire Risk

Explosion Risk
Do NOT change the valve settings.

• This valve has been preset at the

factory.

• Changing valve settings may result in fire

hazard or bodily injury.

• Prevent accidental appliance operation when not

attended.

• Unplug or remove batteries from remote control if

absent or if appliance will not be used for an extended

period of time.

• Property damage possible from elevated

temperatures.

CAUTION