Step 9. wiring the fireplace – Heat & Glo Fireplace 6000TR-OAK User Manual

Page 26

Advertising
background image

Heat & Glo • 6000TR-OAK, 6000TR-OAK-IPI • 383-901 Rev. K • 5/06

30

Step 9. Wiring the Fireplace

NOTE: Electrical wiring must be installed by a licensed

electrician.
CAUTION: DISCONNECT REMOTE CONTROLS IF AB-

SENT FOR EXTENDED TIME PERIODS. THIS WILL PRE-

VENT ACCIDENTAL FIREPLACE OPERATION.
For Standing Pilot Ignition Wiring
Appliance Requirements
This appliance DOES NOT require 110-120 VAC to operate.

WARNING: DO NOT CONNECT 110-120 VAC

TO THE GAS CONTROL VALVE OR THE AP-

PLIANCE WILL MALFUNCTION AND THE

VALVE WILL BE DESTROYED.

!

!

Figure 35. Standing Pilot Ignition Wiring Diagram

Figure 36. Fan Wiring Diagram

Optional Accessories
Optional fan and remote control kits require that 110-120

VAC be wired to the factory installed junction box before

the fireplace is permanently installed.

Wall Switch
Position the wall switch in the desired position on a wall.

Run a maximum of 25 feet (7.8 m) or less length of 18

A.W.G. minimum wire and connect it to the fireplace ON/

OFF switch pigtails.

WARNING: DO NOT CONNECT 110-120 VAC

TO THE WALL SWITCH OR THE CONTROL

VALVE WILL BE DESTROYED.

CAUTION: LABEL ALL WIRES PRIOR TO DISCONNEC-

TION WHEN SERVICING CONTROLS. WIRING ERRORS

CAN CAUSE IMPROPER AND DANGEROUS OPERATION.

VERIFY PROPER OPERATION AFTER SERVICING.

BLACK S2

ON

OFF

ON/OFF

SWITCH

WHITE T2

RED T1

THERMOPILE

GAS VALUE

BLACK S1

3/16” PIGGYBACK CONNECTOR

THERMOCOUPLE

REMOTE SWITCH

PIGTAIL

OPTIONAL WALL SWITCH,

THERMOSTAT OR REMOTE

NOTE: IF ANY OF THE ORIGINAL WIRE

AS SUPPLIED WITH THE APPLIANCE

MUST BE REPLACED, IT MUST BE

REPLACED WITH TYPE 105 C RATED WIRE.

O

JUNCTION BOX

VARIABLE SPEED CONTROL

TEMPERATURE

SENSOR SWITCH

WHT

GRN

BLK

BLK

110-120 VAC

BLOWER

BLOWER RECEPTACLE

BLK

BLK

BLK

BLK

WHT

GROUND

WHT

BLK

BLK

BLK

BLOWER

SENSOR

SWITCH

“FAN”

RECEPTACLE

SPEED

CONTROL