In case of difficulty

Screen is blank.

• Check circuit breaker and reset if necessary.
• Ensure the heating/cooling system is powered up.
• Ensure the furnace door is properly closed.
• Ensure two fresh AAA alkaline batteries are correctly installed.

Temperature settings cannot be
changed.

• The System switch is off.
• You are setting the temperatures outside their allowable ranges:

• Heat: 40 °F to 90 °F (4.5 °C to 32 °C).
• Cool: 50 °F to 99 °F (10 °C to 37 °C).

Cool On or Heat On is flashing.

• The compressor protection delay has been activated. Wait for the

delay to end (maximum of 5 minutes).

HI appears on the screen.

• The ambient (measured) temperature is above 122 °F (50 °C).

LO appears on the screen.

• The ambient (measured) temperature is below 32 °F (0 °C).

E1 appears on the screen.

• The temperature sensor circuit is opened. Replace the thermostat.

E2 appears on the screen.

• The temperature sensor circuit is shorted. Replace the thermostat.