OM-277 Page 18

3-11. Electrical Service Guide

60 Hertz Models

300 Amp Model

450 Amp Model

Input Voltage

200

230

460

575

200

230

460

575

Input Amperes At Rated Output

69

60

30

24

104

90

45

36

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

80

70

35

30

125

110

50

45

Normal Operating 3

100

90

45

35

150

125

70

50

Min Input Conductor Size In AWG/Kcmil

4

6

10

10

2

3

8

8

Max Recommended Input Conductor Length In Feet (Me-
ters)

225

(69)

203

(62)

367

(112)

573

(175)

173

(53)

191

(58)

287

(87)

448

(137)

Min Grounding Conductor Size In AWG/Kcmil

8

8

10

10

6

6

8

10

Reference: 1999 National Electrical Code (NEC)

1 Consult factory for circuit breaker applications.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

50 Hertz Models

300 Amp Model

450 Amp Model

Input Voltage

380

400

440

380

400

440

520

Input Amperes At Rated Output

36

34

31

52.5

51

46

38

Max Recommended Standard Fuse Rating In Amperes

1

Time-Delay

2

45

40

35

60

60

50

45

Normal Operating 3

50

50

45

80

80

70

60

Min Input Conductor Size In AWG/Kcmil

8

8

8

6

6

8

8

Max Recommended Input Conductor Length In Feet (Me-
ters)

370

(113)

409

(125)

495

(151)

342

(104)

379

(115)

303

(92)

423

(129)

Min Grounding Conductor Size In AWG/Kcmil

10

10

10

8

8

8

10

Reference: 1999 National Electrical Code (NEC)

1 Consult factory for circuit breaker applications.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).