12. electrical service guide – Hobart Welding Products IRONMAN 250 User Manual

Page 20

Advertising
background image

OM-192 440 Page 16

3-12. Electrical Service Guide

60 Hz Single

Phase

Input Voltage

200

230

Input Amperes At Rated Output

40

35

Max Recommended Standard Fuse Rating In Amperes

Circuit Breaker

1

, Time-Delay

2

50

40

Normal Operating

3

60

50

Min Input Conductor Size In AWG

4

8

10

Max Recommended Input Conductor Length In Feet (Meters)

108

(33)

94

(29)

Min Grounding Conductor Size In AWG

4

10

10

Reference: 2005 National Electrical Code (NEC) (including article 630)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .

3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table

310.16. If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable requirements.

Y Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard. These

recommendations are for a dedicated branch circuit that applies to the rated output and duty cycle of the welding power source.