Vent clearances and framing, A. pipe clearances to combustibles, B. continue adding vent components – Heat & Glo Fireplace HEAT&GLO ST-36TRB-IPI User Manual

Page 36

Advertising
background image

Heat & Glo • ST-36TRB-IPI, PIER-36TRB-IPI, LCOR-36TRB-IPI, RCOR-36TRB-IPI • 2128-900 Rev. i • 3/13

36

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to
vent. DO NOT pack insulation or other combustibles:

• Between ceiling fi restops
• Between wall shield fi restops
• Around vent system

Failure to keep insulation or other material away from
vent pipe may cause over heating and fi re.

8

8

Vent Clearances and Framing

Figure 8.1 Horizontal Venting Clearances To Combustible
Materials

* When using SLP pipe, minimum clearances from the vent pipe to combustible materi-

als at wall shield firestops are:

Top: 2-1/2 in. (64 mm)

Bottom: 1/2 in. (13 mm)

Sides: 1 in. (25 mm)

Note: Heat shields MUST overlap by a minimum of 1-1/2 in. (38 mm).
‡ DVP heat shield - designed to be used on a wall 4 in. to 7-1/4 in. (102 mm to 184

mm) thick.

‡ ,f wall thickness is less than 4 in. the e[isting heat shields must be field trimmed. ,f

wall thickness is greater than 7-1/4 in. a DVP-HSM-B will be required.

‡ SLP heat shield - designed to be used on a wall 4-3/8 in. to 7-5/8 in. (111 mm to

194 mm thick).

‡ ,f wall thickness is less than 4-3/8 the e[isting heat shields must be field trimmed.

,f wall thickness is greater than 7-5/8 in. a DVP-HSM-B will be required.

(DVP-SLP Pipe Shown)

3 in. (76 mm)
top clearance *

1 in. (25 mm)
clearance
bottom & sides

Heat
Shield

Wall

Shield

Firestop

Heat
Shield

WALL

3 in. (76 mm)
top clearance *

1 in. (25 mm)
clearance
bottom & sides

Heat
Shield

Wall

Shield

Firestop

Heat
Shield

WALL

3 in. (76 mm)

top clearance

1 in. (25 mm)
clearance around
vertical sections

B. Continue Adding Vent Components

WARNING! Risk of Fire! Installation of this appliance
may require the use of heat shield 385-920 above the
fi rst 90

0

elbow in the venting system.

• The heat shield is required above the fi rst elbow if the

clearance to combustible surface above is between
three (3) and four (4) inches. A shield is not required for
clearances greater than four inches. See Figure 8.2.

• Fasten the shield in place using the four pilot holes

provided in the part. The shield should be oriented such
that the 13-1/8 inch dimension (longest dimension) is
running in the same direction the elbow is pointing. The
shield should be centered directly above the elbow, and
positioned so that it creates a 1/2 inch airspace between
the shield and the combustible surface. See Figure 8.3.

Figure 8.2

HEAT

SHIELD

3 in. MIN.

(76 mm)

COMBUSTIBLE

SURFACE

(Required for clearances

between 3 and 4 inches.)