C. facing material, D. finishing material – Heat & Glo Fireplace HEAT&GLO ST-36TRB-IPI User Manual

Page 57

Advertising
background image

Heat & Glo • ST-36TRB-IPI, PIER-36TRB-IPI, LCOR-36TRB-IPI, RCOR-36TRB-IPI • 2128-900 Rev. i • 3/13

57

Figure 13.16 Combustible Mantel Leg or Wall Projections

(Acceptable on both sides of opening)

TOP VIEW

3-1/4 in. Min.

2-3/4

in. Min.

1/2 in.

Min.

Unlimited

1 in.
Max.

FIREPLACE

OPENING

Note: Clearance from opening to perpendicular wall.

C. Facing Material

• Metal front faces may be covered with non-combustible

materials only.

• Facing and/or fi nishing materials must not interfere with

air fl ow through louvers, operation of louvers or doors,
or access for service.

• Facing and/or fi nishing materials must never overhang

into the glass opening.

• Observe all clearances when applying combustible

materials.

• Seal joints between the fi nished wall and appliance top

and sides using a 300 °F minimum sealant. Refer to
Figure 13.17.

WARNING! Risk of Fire! DO NOT apply combustible
materials beyond the minimum clearances. Comply with
all minimum clearances to combustibles as specifi ed in
this manual. Overlapping materials could ignite and will
interfere with proper operation of doors and louvers.

0 in.

0 in.

0 in.

Finish wall material may be
combustible - Top and Sides

High Temperature Sealant (300° F/149° C min.)

Top and Side Seal Joint

Figure 13.17 Noncombustible Facing Diagram

Figure 13.19 Overlap Fit Door

Figure 13.18 Folio Door and Aero

DOOR

FIT

FINISH MATERIAL

MAXIMUM

THICKNESS

SEE FIGURE

Aero

Inside

Any

13.18

Folio

Inside

Any

13.18

Arcadia

Overlap

1 inch

13.19

Inside

Any

13.20

Halston

Overlap

1 inch

13.19

Inside

1 inch - 2 inch

13.21

Chateau

Overlap

1 inch

13.19

Inside

Any

13.20

Valencia

Overlap

1 inch

13.19

Inside

Any

13.20

Galleria

Overlap

1 inch

13.19

Inside

1 inch - 2 inch

13.21

D. Finishing Material

Only doors certifi ed for use with this appliance model may
be used. Contact your dealer for a list of doors that may
be used. Once you have determined what kind of door
and fi nishing material is going to be used on the fi replace,
you may use the table below which shows the door mod-
els and the fi nishing material thickness allowed. For an
inside fi t there is an available template to assist with siz-
ing the fi nishing material.

Stop fi nishing material fl ush with opening.

FINISHING MATERIAL
4 IN. MAXIMUM THICKNESS

DOOR

FINISHING MATERIAL
4 IN. MAXIMUM THICKNESS

1 in. MAX

FINISHING MATERIAL

(TOP EDGE)

DOOR

FRONT FACE OF FIREPLACE

Finishing materials 1 inch maximum thick.

Stop fi nishing material fl ush with opening.

ST-36TRB-IPI

DOOR

FIT

FINISH MATERIAL

MAXIMUM

THICKNESS

SEE FIGURE

Aero

Inside

Any

13.22

Chateau

Inside

Any

13.22

Arcadia

Inside

Any

13.22

PIER-36TRB-IPI