Install to Fit Your Application

TrueDry DR90 Dehumidification System 69-2407—01

5

Flex duct is recommended in connecting to the TrueDRY DR90 collars to reduce vibration noise.

M24745

Electrical requirements:

115 VAC outlet. Ground fault
interrupter (GFI) recommended.

Duct sizing: Use minimum 10-in. diameter round for
duct lengths up to 25 ft. Minimum 12-in. required for
lengths longer than 25 ft. Duct branches from the
main inlet/exhaust should be minimum 10-in. round
for 2-3 branches, and 12-in. round or larger for 4
branches or more.
For the optional fresh air ventilator port, use 6-in.
round, insulated duct for lengths up to 50 ft.
Use 8-in. round duct for more than 50 ft. of if more
than 100 CFM is required.
Isolated Areas: Effective dehumidification may require
ducting to isolated or stagnant air flow areas.

SUPPLY

RETURN

AIR HANDLER

TrueDRY

M27325

A

Main Return to Main Return

Ideal when…
• Running TrueDRY DR90 with A/C

operation.

• Minimizing discharge air temperature

(DAT) increase is preferred.

• Space dictates.

SUPPLY

RETURN

AIR HANDLER

TrueDRY

M27324

BACKDRAFT

DAMPER

B

Main Return to Main supply

Ideal when…
• Running TrueDRY DR90 opposite A/C

operation. Running with A/C operation

requires damper on the exhaust port

to minimize backdraft when TrueDRY

DR90 is not on but A/C is.

• Space dictates.