Freeze Timer (9 & 10)

Water Saver Timer (7 & 8)

Pump-Out Frequency Control

(5 & 6)

Pump-Out Timer (3 & 4)

Harvest Timer (1 & 2)

S1 Dip Switch

S2 Dip Switch

Anti-Slush Control (5 & 6)

Float Switch Selector (2)

Pump-Out/Drain Selector (1)

b) Harvest Timer (S1 dip switch 1 & 2)

Used for adjustment of the harvest timer. The harvest timer starts counting when the
thermistor reads a certain temperature at the evaporator outlet.

Dip Switch Setting

Time

(seconds)

No. 1

No. 2

OFF

OFF

60

ON

OFF

90

OFF

ON

120

ON

ON

180

c) Pump-Out Timer (S1 dip switch 3 & 4)

Once every ten freeze cycles, the drain valve opens to drain the water tank for the time
determined by the pump-out timer. These switches also determine the time to delay
completion of a defrost cycle, i.e. the minimum defrost time.
Do not change this setting, or the unit will not operate properly or produce high quality
ice.

Dip Switch Setting

Time (seconds)

No. 3

No. 4

T1

T2

OFF

OFF

10

120

ON

OFF

10

180

OFF

ON

20

120

ON

ON

20

180

T1: Time to drain the water tank
T2: Harvest timer at pump-out

Refi ll Counter (3 & 4)

* Functions of S2 dip switch nos. 2

through 6 depend on program version.