9 flowconf configuration - pv4 – Honeywell SMV 3000 User Manual

Page 83

Advertising
background image

1/99

SMV 3000 Transmitter User’s Manual

71

6.9

FlowConf Configuration - PV4,

Continued

About LRV and URV

The LRV and URV set the desired zero and span points for your
calculated measurement range as shown in the example in Figure 24.

Figure 24

Typical Volumetric Flow Range Setting Values

Typical Range Configuration for Volumetric Flow

LRL
LRV

SPAN

URV

URL

0

325

650

975

1300 m3/h

Range Limits

Measurement Lower Range Upper Range

Span

Range

Value

Value

0 to 1300 m3/h 0 to 650 m3/h 0 m3/h 650 m3/h

650 m3/h

ATTENTION

The default engineering units for volumetric flow rate is cubic meters
per hour and tonnes per hour is the default engineering units for mass
flow rate.

The URV changes automatically to compensate for any changes in the
LRV and maintain the present span (URV – LRV).

If you must change both the LRV and URV, always change the LRV
first.

Continued on next page