OM-318 Page 12

2-6.

Weld Output Terminals And Selecting Cable Sizes

Total Cable (Copper) Length In Weld Circuit Not Exceeding

100 ft (30 m) Or Less

150 ft

(45 m)

200 ft

(60 m)

250 ft

(70 m)

300 ft

(90 m)

350 ft

(105 m)

400 ft

(120 m)

Weld Output

Terminals

Welding

Amperes

10 – 60%

Duty

Cycle

60 – 100%

Duty

Cycle

10 – 100% Duty Cycle

SMAW/GTAW

100

4

4

4

3

2

1

1/0

1/0

AC/CC (+)

AC/CC (–)

SMAW/GTAW

150

3

3

2

1

1/0

2/0

3/0

3/0

200

3

2

1

1/0

2/0

3/0

4/0

4/0

250

2

1

1/0

2/0

3/0

4/0

2-2/0

2-2/0

300

1

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-3/0

350

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-3/0

2-4/0

CV (+)

CV (–)

FCAW/GMAW

400

1/0

2/0

3/0

4/0

2-2/0

2-3/0

2-4/0

2-4/0

Ref. ST-152 973-A

FCAW/GMAW

500

2/0

3/0

4/0

2-2/0

2-3/0

2-4/0

3-3/0

3-3/0

Weld cable size (AWG) is based on either a 4 volts or less drop or a current density of at least 300 circular mils per ampere.

S-0007-D

2-7.

Remote 14 Receptacle

Socket*

Socket Information

A

24 volts ac. Protected by circuit breaker CB2.

B

Contact closure to A completes 24 volts ac contactor control
circuit.

G

Circuit common for 24 and 115 volts ac circuits.

I

115 volts ac. Protected by circuit breaker CB1.

A

J

B

K

I

J

Contact closure to I completes 115 volts ac contactor control
circuit.

C

L

N

H

D

M

G

E

F

C

Command reference; 0 to +10 volts dc output to remote control.

E

F

D

Remote control circuit common.

Ref. ST-152 973-A

E

0 to +10 volts dc input command signal from remote control.

K

Chassis common.

*The remaining sockets are not used.