8. 115 volts ac duplex receptacle, 9. electrical service guide – Hobart Welding Products 300 DC User Manual

Page 17

Advertising
background image

OM-318 Page 13

2-8.

115 Volts AC Duplex Receptacle

Ref. ST-152 973-A

Y

Turn Off power before con-
necting to receptacle.

1

115 V AC Receptacle

Receptacle is protected from over-
load by circuit breaker CB1 (see
Section 4-2).

Power output is shared between
this receptacle and the Remote 14
receptacle (see Section 2-7).

1

2-9.

Electrical Service Guide

60 Hz

50 Hz

Input Voltage

200

230

460

575

220

380

415

Input Amperes At Rated Output

105

91

46

36

88

51

47

Max Recommended Standard Fuse Or Circuit Breaker Rating In
Amperes

Circuit Breaker

1

, Time-Delay

2

125

110

50

45

110

60

50

Normal Operating

3

150

125

70

50

125

80

70

Min Input Conductor Size In AWG/Kcmil

4

6

8

10

6

8

8

Max Recommended Input Conductor Length In Feet (Meters)

116

(35)

103

(31)

271

(83)

284

(87)

99

(30)

194

(59)

232

(71)

Min Grounding Conductor Size In AWG/Kcmil

6

6

8

10

6

8

8

Reference: 1999 National Electrical Code (NEC)

1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.

2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and

above).

Advertising