Configuring the control parameters, 1 fields – Honeywell Stryker VAV 62-2030-01 User Manual

Page 15

Advertising
background image

STRYKER VAV USER GUIDE

15

62-2030—01

8. CONFIGURING THE CONTROL PARAMETERS

Use this page to set control parameters for an Stryker VAV device that are used to control the damper.

To set Control Parameters:

8.1 Fields

NOTE: The Pressurize, Depressurize, Night Purge,

Emergency Purge and Morning Warmup values

are configured as a percentage of maximum flow

(pressure independent) or as percentage of

damper position (Pressure dependant).

Step

Action

1

From the left pane of the

VAV Configuration Wizard, select Control Parameters.

2

Enter information in the available fields.

3

Click

Undo All to revert to the last saved settings.

4

Click

Next to display the Schedule page.

5

Click

Finish to save settings to station.

Table 9. Configuring the Control Parameter Fields.

Name

Definition

Maximum Flow Position

VAV Box Maximum damper position. Applies only to pressure dependent control mode or when a

pressure independent airflow sensor fails.

Standby Flow Position

VAV Box minimum damper position used during standby mode. Applies only to pressure

dependent control mode.

Minimum Flow Position

Zone terminal minimum cooling damper position during the occupied mode of operation. Applies

only to pressure dependent control mode or when a pressure independent airflow sensor fails.

Reheat Flow Position

VAV Box maximum damper position in Reheat mode. The cooling air damper will be at this position

at maximum reheat capacity.

Window Open

Window open damper position. When a window is open, air flow control is disabled and the flow

damper is set to this position until the space temperature drops below the temperature set point.

Night Purge

Night purge damper setting.

Morning Warmup

Warmup damper setting.

Morning Warmup Type

Enables you to select the morning warmup type to be used when a 'MorningWarmup' command is

received by the controller.

Mixed Air: The temperature control is turned off, and the damper is controlled as per the Warmup

setting.

Warm Air with Reheat: Warm air is being supplied via the duct and the temperature control is

reverse acting. ReHeat and peripheral may be turned on.

Warm Air without Reheat: Warm air is being supplied via the duct and the temperature control is

reverse acting. ReHeat is disabled however peripheral heat may be used.

Pressurize

Damper setting to be used when a Pressurize Command is received over the network for smoke

control operation.

Depressurize

Damper setting to be used when a De-Pressurize Command is received over the network for

smoke control operation.

Emergency Purge

Damper setting to be used when an Emergency Purge Command is received over the network.

Unoccupied Minimum

Flow Position

Minimum damper position to be used during unoccupied mode.

Advertising