9. CONFIGURING THE PID

Use this page to configure the PID parameters for both the heating and cooling loops in a Stryker VAV device.

To set PID:

9.1 Fields

Flow Tracking Offset

Represents the flow tracking offset value used when FlowType is configured as FlowTracking. This

offset is added to the value of nviFlowTrack to determine the flow setpoint.

Terminal load calculation Enables you to perform the terminal load calculation. You have the option to select 0 or 1 in the

Terminal load calculation field.

Select 0 to use the conventional zone terminal load calculation.

The conventional zone terminal load calculation uses the PID output of heating and cooling

controls. When the controller is switched to the heating mode, the Terminal load is ? 0.

Select 1 to use the CZS zone terminal load calculation.

The CZS zone terminal load calculation uses the proportional output of heating and cooling

controls. When the controller is switched to the heating mode, the Terminal Load continues to

report both heating and cooling demand. The terminal load absolute value is truncated at 100%.

Table 9. Configuring the Control Parameter Fields. (Continued)

Name

Definition

Step

Action

1

From the left pane of the

VAV Configuration Wizard, select PID.

2

Enter information in the available fields.

3

Click

Next to display the Accessory Loops page.

4

Click

Undo All to revert to the last saved settings.

5

Click

Finish to save settings to station.

Table 10. PID Names.

Name

Definition

Cooling Throttling

Range

Value must be between 2 to 30 DDF.

Cooling Integral Time

Value must be between 0 to 9000 sec.

Cooling Derivative

Time

Value must be between 0 to 9000 sec.

Heating Throttling

Range

Value must be configured based on reheat configuration.

Reheat Type

TR (DegF)

modulating

5

1 stage

3

2 stage

4

3 stage

7

4 stage

8