STRYKER VAV USER GUIDE

21

62-2030—01

Sylkbus Alarm: The Sylkbus communication alarm occurs

when the communication link between the Sylk sensor and

the controller is lost or when the Sylk sensor is configured with

the wrong address.

To communicate successfully with an Stryker VAV device,

TR71/TR75 devices must be configured with the address 1.

To communicate successfully with an Stryker VAV device,

C7400S sensors must be configured with the address 8.

5Node disabled Error: The node disabled error is reported

when the control execution is disabled.

For example, this error is reported when the controller is

commanded to manual mode.

RELATED TOPICS

“1. About Stryker VAV” on page 2

“2. Configuration” on page 4

13. DIAGNOSTICS

Use this page to test the outputs of an Stryker VAV device in

manual mode. This action can be performed with the device in

online mode. The device must be in downloaded state.

The Diagnostics screen displays:

• All configured Digital Outputs to command ON/OFF

• All configured Analog Outputs to command the values

between 0 to 100%

• The values that are sensed (currently) at the outputs

To diagnose an Stryker VAV device:

13.1 Fields

Table 12. Diagnostic Fields.

RELATED TOPICS

“1. About Stryker VAV” on page 2

“2. Configuration” on page 4

Step

Action

1

From the

Nav menu, choose Station > Driver > LON network > AscLonVAV device.

2

Right-click the device and choose

Views > Diagnostics from device items. The Diagnostics screen appears.

3

Enter information in the available fields.

4

Click

Refresh to reset the settings.

5

Click

Set to set the output values for diagnosis.

Name

Definition

Name

Displays the configured parameter names.

Modulating Output

Diagnostics

The number of Modulating Outputs depends on the outputs configured in the application.

Current Value: Displays the value of the modulating output as read from the controller. This

field is non-editable.

Edit Value: Enter the value that the output must be commanded to. The range is 0-100 %.

Binary Output Diagnostics

The number of Binary Outputs depends on the outputs configured in the application.

Current Value: Displays the value of the modulating output as read from the controller. This

field is non-editable.

Edit Value: Select ON or OFF.

Set

Click

Set. The controller is set to 'Manual' control and the commanded output values are written

to the controller.

NOTE: Note: If the controller is in Auto mode, click Set to set the controller to Manual

mode.

Auto Refresh

Select the

Auto Refresh checkbox to automatically refresh the output values every 30 seconds.

Refresh

Select the

Refresh to refresh the output values, only when the device is in manual mode.

Current Mode

Displays the current mode of the device.