Fluke HART 744 User Manual

Page 26

Advertising
background image

744
HART Mode Users Guide

18

2. Use

the

u

and

d

keys to select the Sensor Trim

operation, and press

e

.

3. Follow the instructions on the display. For pressure,

there is a message to connect a pressure module to
the calibrator, and another to press the

c

key to

zero the pressure module.

4. Press

Continue

.

pe18s.bmp

5. Enter the trim value you want the calibrator to

produce, and press

e

, or in the case of a

pressure transmitter (as above), press

Fetch

to load

the value being measured by the Fluke pressure
module into the dialog box.

6. Press

Trim

.

7. If prompted to do so, repeat steps 2 and 3, following

the prompts on the display, to trim the remaining
points.

Note

Select trim points near the range limits unless the
transmitter’s documentation specifies otherwise.

If you get an error message that for the selected
trim point there is an excess correction,
sometimes you can solve the problem by doing a
series of Sensor Trims in small steps from the
previous trim point toward the desired trim point.