Installation instructions, Exhausting the dryer (cont.) warning, Example only – GE DPGT750 User Manual

Page 30

Advertising
background image

EQUIVALENT

RIGID

NUMBER

EQUIVALENT

DUCT PIECES

LENGTH

X

USED

=

LENGTH

Rigid Metal

1 Ft.

X

(4)

=

4 Ft.

Ducting
(Preferred)

Elbows

10 Ft.

X

(3)

=

30 Ft.

(90°/45°)

Turns Less

2 Ft.

X

(1)

=

2 Ft.

Than 4 Ft.

Rigid Ducting

1 Ft.

X

(5)

=

5 Ft.

4” Wall Cap

5 Ft.

X

(1)

=

5 Ft.

Total Ductwork Length

=

46 Ft.

TOTAL MUST BE LESS THAN OR EQUAL TO 150 FT.

Installation Instructions

30

EXHAUSTING THE DRYER (cont.)

WARNING

USE ONLY METAL 4” DUCT. DO NOT USE
DUCT LONGER THAN SPECIFIED IN THE
EXHAUST LENGTH TABLE.

Ducting longer than 150 equivalent feet will:

Increase the drying times and the energy

cost.

Reduce the dryer life.
Accumulate lint, creating a potential fire

hazard.

EXAMPLE ONLY

The following chart describes an example of
one possible ductwork installation.

The correct exhaust installation is your
responsibility.

Problems due to incorrect installation are not
covered by the warranty.

The length of the exhaust system depends
upon the type of duct, number of turns and
the type of exhaust hood (wall cap), and all
conditions noted below. Both rigid and flexible
metal ducts are shown in the table.

For satisfactory air movement, the total duct
length should not exceed 150 equivalent feet.

4”

(10.2 cm)

TRANSITION

DUCTING

(DR

YER TO W

ALL)

INSIDE W

ALLS/CEILING

(W

ALL TO W

ALL CAP)

W

ALL

CAPS

Less Than 4 Ft.