-12-

Model g0442/g0601 (Mfg since 3/12)

g0601 circuit requirements for

220v

the Model g0601 is prewired to operate on a
220v power supply circuit that has a verified
ground and meets the following requirements:

nominal voltage ........................................220v

cycle ..........................................................60 hz

phase .................................................... 3-phase

circuit rating ................. time delay 30 amps

connection ......hardwire with locking switch

g0601 circuit requirements for

440v

the Model g0601 can be converted to operate on
a 440v power supply.

g0601 440v conversion

instructions are provided on

page 13. the intend-

ed 440 circuit must have a verified ground and
meet the requirements that follow:

nominal voltage ........................................440v

cycle ..........................................................60 hz

phase .................................................... 3-phase

rated size .......................time delay 20 amps

connection ......hardwire with locking switch

connection type

figure 2. typical setup of a permanently

connected machine.

Power

Source

Locking

Disconnect Switch

Machine

Ground

Ground

Conduit

Conduit

A permanently connected (hardwired) power sup-
ply is typically installed with wires running through
mounted and secured conduit. A disconnecting
means, such as a locking switch (see following

Figure), must be provided to allow the machine
to be disconnected (isolated) from the power
supply when required. This installation must be
performed by an electrician in accordance with all
applicable electrical codes and ordinances.

extension cords

Since this machine must be permanently con-
nected to the power supply, an extension cord
cannot be used.

Serious injury could occur if you connect

the machine to power before completing the

setup process. DO NOT connect to power

until instructed later in this manual.

grounding instructions

In the event of a malfunction or breakdown,
grounding provides a path of least resistance
for electrical current to reduce the risk of electric
shock. A permanently connected machine must
be connected to a grounded metal permanent wir-
ing system; or to a system having an equipment-
grounding conductor. All grounds must be verified
and rated for the electrical requirements of the
machine. Improper grounding can increase the
risk of electric shock!