3.1 Maximum cable cross section for regulator terminals

Maximum Permissible Cable Cross-Section

Tightening

[mm

2

]

torque

flexible

multi-core

[Nm]

1...79

0.14...1.5

0.14...1.5

28...16

0.4

80...85

0.14...1.5

0.14...1.5

28...16

0.4

Ai4090

AWG

Terminals

NOTE:

Terminal board points are intended for 1 wire/point.

Daisy chains and multiple wires/point are better done with a panel mounted terminal board.

4. power terminals

F unction

max volts/curr.

Motor ground connection

Braking unit resistor command (braking resistor

must be connected between BR1 and C)

DC Bus circuit connection

770 VDC/ 1.65 X

output current

A C line voltage

480 VAC

+10% 3Ph

See table 2.4.2.1

Motor connection

A C line volt 3Ph

1.36 X output

current

Braking resistor (optional)

M

3Ph ~

PE1/

Grounding (protective earth) conductor

U1/L1

V1/L2

W1/L3

BR1

U2/T1

V2/T2

W2/T3

C

D

PE2/

4.1 Maximum cable cross section for power terminals

Hp

3/4

1

2

3

5

7.5

10

15

20

25

30

AWG

12

8

4

[mm2]

8

10

16

25

Tightening torque

[Nm]

2

3

AWG

12

8

6

[mm2]

8

10

16

16

Tightening torque

[Nm]

2

3

Hp

40

50

60

75

100

125

150

200

AWG

1/0

2/0

4/0

300*

350*

4xA WG2

*=kcmils

[mm2]

50

70

95

150

185

4x35

Tightening torque

[Nm]

AWG

[mm2]

Tightening torque

[Nm]

3

ai4040

35

6

16

14

2

10

4

0.5 to 0.6

6

1.2x1.5

14

2

6

10

U1, V1, W1, U2, V2, W2 ,C ,D
terminals

PE1, PE2 terminals

U1, V1, W1, U2, V2, W2, C, D
terminals

PE1, PE2 terminals

4

1.2x1.5

0.5 to 0.6

4

2

2

50

4

12

10-30