GE AV-300i User Manual

Page 21

Advertising
background image

21

Control buttons

Jog

Shift

Sequencing

Press START button to command the Drive to the Enable and
Run state

Press STOP button commands to stop the Drive from the
Run state

Press to display the current reference value and to increase
the reference value and accelerate the drive.

Press to decrease the reference value and decelerate the drive.

Press SHIFT and [-] to change the motor shaft rotation

Display

Motor pot oper.

+0 [rpm] POS

Motor pot oper.

-0 [rpm] NEG

8.1 Motor Potentiometer function

Note!

(Main commands = DIGITAL)
Enable drive, terminal 12 connected to 24VDC
Start, terminal 13 connected to 24VDC

Resetting the speed reference value using Mot pot
function

Press [STOP] button to stop the motor

Press [Left arrow] until to “Basic menu”, then [Down
arrow]
to “Functions”. [Enter] to motor pot, then
[Enter] to “enab motor pot”, press [Down arrow] to
motor pot reset, then [Enter].

The diplay will read “ready” until the reference value
is set to zero.

Set the motor pot to “disable” (Enable motor pot
parameter = Disable) if you will want to use an analog
voltage on terminal 1 for speed reference.

Jog function

Note!

This function is enabled as a default setting (Enable jog
parameter = Enabled). Speed reference value = 100 rpm.

(Main commands = DIGITAL)

Enable drive, terminal 12 connected to to 24 VDC

Start, terminal 13 conected to to 24 VDC

Press [SHIFT and [+] to run, the speed will be displayed

Press [-] to select the motor shaft rotation

Press [jog] to run the other direction

Press [Left arrow] to exit from jog operation

Changing jog reference

Press [Down arrow] until “Functions”, [Enter], then [Down
arrow]
until “Jog reference”, [Enter], using the [Up arrow]/
[Down arrow] keys to change the value and the [Left
arrow]
to move the character position, set the reference
value, then [Enter].

If there are other changes you might want to make to set
up (see Options), do them now, and complete the following
step to put everything into permanent memory.

Saving all values to Permanent Memory:

Press [Left arrow] back to “Configuration” then [Up
arrow]
to “basic menu” and [Enter]. Press [Down
arrow]
to “save parameters” and [Enter]. Parameters
are now stored permanently.

Advertising