Goodman Mfg GKS9 User Manual

Page 10

Advertising
background image

10

Fu rnace

Water
Heater

Outlet Air

Chimney o r Gas Vent

NOTE: The inlet and outlet air
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total input rating of all equipment
in the enclosure.

Inlet air duct
[ends 1 ft (3 00 mm)
above floor]

Ventilation louvers
(each end of attic)

Equipment Located in Confined Spaces; All Air from Outdoors

Through Ventilated Attic. See 5.3.3-b.

3. When communicating with the outdoors through horizontal ducts,

each opening shall have a minimum free area of 1 square inch per
2,000 BTU per hour of total input rating of all equipment in the
enclosure.

Furnace

Water
Heater

Chimney or Gas Vent

NOTE: The air duct openings
must have a free area of not
less than one square inch per
2000 BTU of the total input
rating of all equipment in the
enclosure*.

Outlet air duct

Inlet air duct

*If the appliance room is located against an outside wall and the air openings communicate directly with the
outdoors, each opening shall have a free area of not less than one square inch per 4,000 BTU per hour of
the total input rating of all appliances in the enclosure.

Equipment Located in Confined Spaces; All Air from Outdoors.

See 5.3.3-b.

4. When ducts are used, they shall be of the same cross-sectional

area as the free area of the openings to which they connect. The
minimum dimension of rectangular air ducts shall not be less
than 3 inches.

Furnace

Water
Heater

Opening

Chimney or Gas Vent

NOTE: The single opening must have
a free area of not less than one
square inch per 3000 BTU of
the total input rating of all equip-
ment in the enclosure, but not less than
the sum of the areas of all vent
connectors in the confined space.

Alternate
Opening
Location

Equipment Located in Confined Spaces; All Air from Outdoors -

Single Air Opening. See 5.3.3-b.

space shall be considered in making this determination. Each open-
ing shall have a minimum free area of 1 square inch per 1,000 BTU
per hour of the total input rating of all gas utilization equipment in
the confined space, but not less than 100 square inches. One open-
ing shall be within 12 inches of the top and one within 12 inches of
the bottom of the enclosure.

Furnace

Water
Heater

Opening

Chimney or Gas Vent

Opening

NOTE: Each opening must have
a free area of not less than one
square inch per 1000 BTU of
the total input rating of all equip-
ment in the enclosure, but not
less than 100 square inches.

Equipment Located in Confined Spaces; All Air from Inside

Building. See 5.3.3-a.

(b) All Air from Outdoors: The confined space shall be provided with

two permanent openings, one commencing within 12 inches of the
top and one commencing within 12 inches of the bottom of the
enclosure. The openings shall communicate directly, or by ducts,
with the outdoors or spaces (crawl or attic) that freely communicate
with the outdoors.

1. When directly communicating with the outdoors, each opening

shall have a minimum free area of 1 square inch per 4,000 BTU
per hour of total input rating of all equipment in the enclosure.

Furnace

Water
Heater

Outlet Air

Chimney or Gas Vent

NOTE: The inlet and outlet air
openings must each have a free
area of not less than one square
inch per 4000 BTU of the
total input rating of all equipment
in the enclosure.

Inlet Air

Ventilation louvers for
unheated crawl space

Alternate
air inlet

Ventilation louvers
(each end of attic)

Equipment Located in Confined Spaces; All Air from Outdoors—

Inlet Air from Ventilated Crawl Space and Outlet Air to Ventilated

Attic. See 5.3.3-b

2. When communicating with the outdoors through vertical ducts,

each opening shall have a minimum free area of 1 square inch per
4,000 BTU per hour of total input rating of all equipment in the
enclosure.

Advertising